FAQ
Here you can find a number of questions and answers regarding our products.
Here you can find a number of questions and answers regarding our products.
The reset button is located between the supply voltage connection and Ethernet 1.

The button is located under the lid and can be reached with a small screwdriver. However, use caution and do not use a pointed screwdriver that could end up next to the button.
The reset button allows you to restart the PiiGAB M-Bus 900, set the network settings to default (DHCP plus random IP address) or change the web login to default (Admin, Admin).
The reset button should be used as follows. Press the button until the selected LED is lit, when the LED flashes rapidly, press the button again and the selected function will be executed.
Example: Press the button once to switch on P1 (Rx). Wait for P1 (Rx) to flash quickly and then press the button again. If you press the button while it is flashing rapidly, the PiiGAB M-Bus 900S/T will automatically restart. If you do not press while the light is flashing, nothing will happen.
The table below describes the functions of the button:
| Restart | Press the button 1 time and wait until the P1/Tx LED flashes rapidly. Then press the button an additional time while it is flashing | The device is restarted. |
| Resetting IP settings | Press the button 1 time and wait until the P1/Tx LED flashes rapidly. Then press the button an additional time while it is flashing. | The Ethernet port of the device returns to its original settings. DHCP and randomised IP if there is no DHCP server available. |
| Resetting passwords | Press the button 6 times and wait until the P3/Rx line flashes rapidly. Then press the button an additional time while it is flashing. | If a password has been selected for the login, it now returns to Admin : Admin |
Here is an example of how to setup the initial contact with a PiiGAB M-Bus 900.
Now you should see the PiiGAB M-Bus Setup display show the PiiGAB M-Bus 900 in the list. Check the MAC-address and the IP-address should be 192.168.10.2.
Yes. The license can be changed without replacing the gateway.
Some meters do not handle SND_NKE together with REQ_UD2. Untick the SND_NKE option and the meters should respond.
Check that the supply voltage (24VAC / DC) to the converter is fully isolated from other products in your control panel. Also check the ground on the primary and secondary sides of the protection transformer so that they are not interconnected.
Check that the supply voltage (24VAC / DC) to the converter is fully isolated from other products in your control panel. Also check the ground on the primary and secondary sides of the protection transformer so that they are not interconnected.
To troubleshoot M-Bus meters connected to an PiiGAB M-Bus 810 there are a couple of things to verify.
Here is a list of good tools to use during troubleshooting:
IP-address
What IP-address is the gateway using? To have network communication with the gateway you need to setup your computer in the same network as the gateway. If there is an IT section please contact them to receive an IP-address for your computer. With the PiiGAB M-Bus Setup Wizard you can search gateways on the network or ping the gateway’s IP-address to verify if the network communication works.
In the PiiGAB M-Bus Wizard, you can search for converters on the network or "ping" the IP address of the converter to verify that the network connector is working.
f it’s not possible to receive the gateway’s IP-address then you need to setup a new IP-address.
Please see the FAQ on how to do this.
Harbour
What port is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the port with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Protocol
What protocol is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the protocol with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Note: If the gateway uses TCP you might not be able to connect to the gateway with the PiiGAB M-Bus Setup Wizard to read the M-Bus meters. This is due to that another client is connected to the port that the gateway is using. Change the port, change to UDP or turn off the client.
Communication speed
What communication speed is the gateway set to in order for the the M-Bus client to read the M-Bus meters?If you have network connection with the gateway you can find out the communication speed with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Note: If the gateway is set to 300 baud the communication speed is very slow. Remember to change the timeout in the PiiGAB M-Bus Setup Wizard to handle the long response time.
M-Bus meters
Is there any documentation of what M-Bus meters that are connected to the gateway? What addresses does the M-Bus meters use? (primary or secondary addresses).
If there is documentation of the meters then you can simple check each meter one by one with the PiiGAB M-Bus Setup Wizard. It’s also possible to read the search function in the PiiGAB M-Bus Setup Wizard.
If there is no documentation of the meters then you can use the search function in the PiiGAB M-Bus Setup Wizard. If the the result of the search function is incomplete then you have to find each meter one by one on the site and test them individually by it’s M-Bus address (primary or secondary address).
A M-Bus meter not responding
If an M-bus meter is not responding then you have to test the meter individually. If possible disconnect all other meters and test only that specific meter. Try with primary address 254 or the meter’s own primary or secondary address.
If it’s not possible to disconnect all meters then you can test the specific meter with a MicroMaster USB.
On the menu in the gateway's interface, click on "Administrations" under which there is then the submenu "Basic settings". Scroll down a bit on the page and you will get to "Webserver Setting", see screenshot.

If nothing else has been specified in the order, the default configurations are set for DHCP.
All configurations are made in the gateway’s web interface.
At least one can be specified. If a meter does not respond after a re-query, an additional re-query is unlikely to help.
The following list will explain how to install a license in the PiiGAB M-Bus 900/900S. These steps will also show the current license of a PiiGAB M-Bus 900/900S.

The following list will explain how to install software in the PiiGAB M-Bus 900 V2 and PiiGAB M-Bus 900S. These steps are either used to install a new software or update an existing.
Note: If QuickPost, Modbus2MBus or Wireless M-Bus is not shown in the web browser, please press CTRL + F5.
If the communication does not work, check that no other process locks that port.
Check that Modbus2Mbus or any slave port is not set to RS485.
Also enable RS-485 Failsafe in MBushub for more stable collection.

Only PiiGAB M-Bus 900 V2.XX.XX.XXX or later versions support the function where the IP address can be changed with the PiiGAB M-Bus Wizard.
Both PiiGAB M-Bus 900 V2 and PiiGAB M-Bus 900S can change their IP address with the PiiGAB M-Bus Wizard.
Keep in mind that the netmask and default gateway will not be set. These need to be set in the converter's web interface. Please read it under the FAQ section "Example of initial contact"
Yes you can download the new update even if you are using http, but you will need to change the configuration so that http is the default before updating, however we recommend that you use HTTPS instead for security reasons. Valid from version 2.6.2
Here's how to change from HTTP to HTTPS in the gateway, click here
If you don't know whether you're running HTTP or HTTPS, you can download our script to find out. Download it here
If you are using TCP and the M-Bus Wizard at the same time you cannot make contact with an additional TCP client since the M-Bus Wizard “owns” the TCP handle. Shut down the M-Bus Wizard before starting the second TCP client. The same goes if you are using COM ports.
Quick start Guide to Configure M-Bus to Modbus
1. Plug all the meters you want to use on the M-bus loop into Mbus Master ports 1-4 on your Gateway.
2. Search your meters in the web interface using a "Fast Search" in the Startup Config tab

Your meters should appear in a list under the "Fast Search" button
3. Go to the overview page in Startup Config where the meters should now be visible in the list below.

Add Encryption Keys to the meters if they are Wireless meters
4. Click on "Auto-Create Myconfig files"

The files to be used to read meters are now created
5. Go to MbusHub and the tab "Master port", then select the configuration file for the Master port file as shown below. Save the configuration.

6. Go to Slave Port 1 and select the configuration file as shown below

7. Now you will be able to query against the registry entries described in the CSV file located in the slave ports tab of the web interface

Conversion of Modbus meters to M-Bus is done in the program Modbus2Mbus Config. You can find this for download at https://www.piigab.com/products/mjukvara/
In order to have a simple and trouble-free conversion, it is important to have the meter's manual available.
Create a new project and then add a device per meter.
Set the parameters for Mbus and Modbus communication
Add objects for each measured value to be read out and set the correct Modbus register as well as unit and scaling.
If you have several meters of each type, copy the meter and only change the Slave and M-Bus address.
It is also possible to save these as templates for future projects.
After the project is finished, it is saved and then uploaded to the 900
Read M-Bus meters from external M-Bus master
The following list instructs how to configure a PiiGAB M-Bus 900/900S as an M-Bus slave, i.e. one or two external M-Bus masters can read the M-Bus meter connected to the gateway.
Notice: On PiiGAB M-Bus 900 there can only be one external M-Bus master connected.
The picture shows Slave port 2 is configured for M-Bus slave 1 on 2400 baud, 8 data bits, even parity, 1 stop bit, 2000ms as timeout and M-Bus communication. M-Bus Slave 1 at 2400 baud, 8 data bits, even parity, 1 stop bit, 2000ms timeout and M-Bus communication.

Note:

The following list instructs how to configure a PiiGAB M-Bus 900/900S so that M-Bus meters can be read with RS232.
The picture shows Slave port 2 is configured for RS232 on 2400 baud, 8 data bits, even parity, 1 stop bit, 2000ms as timeout and M-Bus communication.

Note:

The following list instructs how to configure a PiiGAB M-Bus 900/900S so that M-Bus meters can be read with RS485.
The picture shows Slave port 2 is configured for RS485 on 2400 baud, 8 data bits, even parity, 1 stop bit, 2000ms as timeout and M-Bus communication.

Note:

If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
| 300 baud rate | 2400 baud rate | 9600 baud rate | |
| Master port | 9600ms | 1300ms | 400ms |
| Slave port | 9600ms | 1300ms | 400ms |
| SND_NKE | 11000ms | 1500ms | 600ms |
| REQ_UD2 | 11000ms | 1500ms | 600ms |
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
| 300 baud rate | 2400 baud rate | 9600 baud rate | |
| Master port | 9600ms | 1300ms | 400ms |
| Slave port | 9600ms | 1300ms | 400ms |
| SND_NKE | 11000ms | 1500ms | 600ms |
| REQ_UD2 | 11000ms | 1500ms | 600ms |
If the converter is set to static IP address, a name server must be specified. This is done on the PiiGAB M-Bus 900 configuration page and in Name Server static IP address field.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
There are two possible cases when the Pwr LED is flashing.
In the event where the M-Bus loop is connected to the pulse port by mistake instead of the M-bus port on a meter a flash can occur every time a pulse goes trough. If the meter generates many pulses the power light will flash very fast as the pulses go through.
The gauges in the Overview page of the web interface have three different status modes.
These do not change automatically but require the user to test the status via the Verify function which tests all meters that are Red or via the Read All Meters function which sends a query to all listed meters to see if they are connected.

A client is something which requests the data from the M-Bus meter through the gateway.
The license depends on the number of load units, clients, protocols and hardware add-ons for which the converter is to be configured.
Quantity of M-Bus loads: 5, 20, 60 eller 120.
Quantity of clients: 1, 2 or 4.
Protocols:
The actual IP-address of the name server. Not the name of the server.
Port 30718 over UDP/IP is used in the following functions:
Other functions in the PiiGAB M-Bus Wizard you specify yourself which port and protocol to use.
Specific to Find converters on the network
Functions Find gateways on your network. uses the broadcast address (255.255.255.255) to find the PiiGAB M-Bus 810 and PiiGAB M-Bus 900/900S on the network. Keep in mind that broadcast may be disabled in routers. This can cause not being able to find converters that are placed on other subnets.
Check that the supply voltage (24VAC / DC) to the converter is fully isolated from other products in your control panel. Also check the ground on the primary and secondary sides of the protection transformer so that they are not interconnected.
To troubleshoot M-Bus meters connected to an PiiGAB M-Bus 810 there are a couple of things to verify.
Here is a list of good tools to use during troubleshooting:
IP-address
What IP-address is the gateway using? To have network communication with the gateway you need to setup your computer in the same network as the gateway. If there is an IT section please contact them to receive an IP-address for your computer. With the PiiGAB M-Bus Setup Wizard you can search gateways on the network or ping the gateway’s IP-address to verify if the network communication works.
In the PiiGAB M-Bus Wizard, you can search for converters on the network or "ping" the IP address of the converter to verify that the network connector is working.
f it’s not possible to receive the gateway’s IP-address then you need to setup a new IP-address.
Please see the FAQ on how to do this.
Harbour
What port is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the port with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Protocol
What protocol is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the protocol with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Note: If the gateway uses TCP you might not be able to connect to the gateway with the PiiGAB M-Bus Setup Wizard to read the M-Bus meters. This is due to that another client is connected to the port that the gateway is using. Change the port, change to UDP or turn off the client.
Communication speed
What communication speed is the gateway set to in order for the the M-Bus client to read the M-Bus meters?If you have network connection with the gateway you can find out the communication speed with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Note: If the gateway is set to 300 baud the communication speed is very slow. Remember to change the timeout in the PiiGAB M-Bus Setup Wizard to handle the long response time.
M-Bus meters
Is there any documentation of what M-Bus meters that are connected to the gateway? What addresses does the M-Bus meters use? (primary or secondary addresses).
If there is documentation of the meters then you can simple check each meter one by one with the PiiGAB M-Bus Setup Wizard. It’s also possible to read the search function in the PiiGAB M-Bus Setup Wizard.
If there is no documentation of the meters then you can use the search function in the PiiGAB M-Bus Setup Wizard. If the the result of the search function is incomplete then you have to find each meter one by one on the site and test them individually by it’s M-Bus address (primary or secondary address).
A M-Bus meter not responding
If an M-bus meter is not responding then you have to test the meter individually. If possible disconnect all other meters and test only that specific meter. Try with primary address 254 or the meter’s own primary or secondary address.
If it’s not possible to disconnect all meters then you can test the specific meter with a MicroMaster USB.
If you are using TCP and the M-Bus Wizard at the same time you cannot make contact with an additional TCP client since the M-Bus Wizard “owns” the TCP handle. Shut down the M-Bus Wizard before starting the second TCP client. The same goes if you are using COM ports.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
In the event where the M-Bus loop is connected to the pulse port by mistake instead of the M-bus port on a meter a flash can occur every time a pulse goes trough. If the meter generates many pulses the power light will flash very fast as the pulses go through.
Some meters do not handle SND_NKE together with REQ_UD2. Untick the SND_NKE option and the meters should respond.
To troubleshoot M-Bus meters connected to an PiiGAB M-Bus 810 there are a couple of things to verify.
Here is a list of good tools to use during troubleshooting:
IP-address
What IP-address is the gateway using? To have network communication with the gateway you need to setup your computer in the same network as the gateway. If there is an IT section please contact them to receive an IP-address for your computer. With the PiiGAB M-Bus Setup Wizard you can search gateways on the network or ping the gateway’s IP-address to verify if the network communication works.
In the PiiGAB M-Bus Wizard, you can search for converters on the network or "ping" the IP address of the converter to verify that the network connector is working.
f it’s not possible to receive the gateway’s IP-address then you need to setup a new IP-address.
Please see the FAQ on how to do this.
Harbour
What port is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the port with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Protocol
What protocol is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the protocol with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Note: If the gateway uses TCP you might not be able to connect to the gateway with the PiiGAB M-Bus Setup Wizard to read the M-Bus meters. This is due to that another client is connected to the port that the gateway is using. Change the port, change to UDP or turn off the client.
Communication speed
What communication speed is the gateway set to in order for the the M-Bus client to read the M-Bus meters?If you have network connection with the gateway you can find out the communication speed with the PiiGAB M-Bus Setup Wizard.
Start the PiiGAB M-Bus Wizard -> Change converter parameters -> Connect via network.
Note: If the gateway is set to 300 baud the communication speed is very slow. Remember to change the timeout in the PiiGAB M-Bus Setup Wizard to handle the long response time.
M-Bus meters
Is there any documentation of what M-Bus meters that are connected to the gateway? What addresses does the M-Bus meters use? (primary or secondary addresses).
If there is documentation of the meters then you can simple check each meter one by one with the PiiGAB M-Bus Setup Wizard. It’s also possible to read the search function in the PiiGAB M-Bus Setup Wizard.
If there is no documentation of the meters then you can use the search function in the PiiGAB M-Bus Setup Wizard. If the the result of the search function is incomplete then you have to find each meter one by one on the site and test them individually by it’s M-Bus address (primary or secondary address).
A M-Bus meter not responding
If an M-bus meter is not responding then you have to test the meter individually. If possible disconnect all other meters and test only that specific meter. Try with primary address 254 or the meter’s own primary or secondary address.
If it’s not possible to disconnect all meters then you can test the specific meter with a MicroMaster USB.
Only PiiGAB M-Bus 900 V2.XX.XX.XXX or later versions support the function where the IP address can be changed with the PiiGAB M-Bus Wizard.
Both PiiGAB M-Bus 900 V2 and PiiGAB M-Bus 900S can change their IP address with the PiiGAB M-Bus Wizard.
Keep in mind that the netmask and default gateway will not be set. These need to be set in the converter's web interface. Please read it under the FAQ section "Example of initial contact"
If you are using TCP and the M-Bus Wizard at the same time you cannot make contact with an additional TCP client since the M-Bus Wizard “owns” the TCP handle. Shut down the M-Bus Wizard before starting the second TCP client. The same goes if you are using COM ports.
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
| 300 baud rate | 2400 baud rate | 9600 baud rate | |
| Master port | 9600ms | 1300ms | 400ms |
| Slave port | 9600ms | 1300ms | 400ms |
| SND_NKE | 11000ms | 1500ms | 600ms |
| REQ_UD2 | 11000ms | 1500ms | 600ms |
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
| 300 baud rate | 2400 baud rate | 9600 baud rate | |
| Master port | 9600ms | 1300ms | 400ms |
| Slave port | 9600ms | 1300ms | 400ms |
| SND_NKE | 11000ms | 1500ms | 600ms |
| REQ_UD2 | 11000ms | 1500ms | 600ms |
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Port 30718 over UDP/IP is used in the following functions:
Other functions in the PiiGAB M-Bus Wizard you specify yourself which port and protocol to use.
Specific to Find converters on the network
Functions Find gateways on your network. uses the broadcast address (255.255.255.255) to find the PiiGAB M-Bus 810 and PiiGAB M-Bus 900/900S on the network. Keep in mind that broadcast may be disabled in routers. This can cause not being able to find converters that are placed on other subnets.
The following list will explain how to install a license in the PiiGAB M-Bus 900/900S. These steps will also show the current license of a PiiGAB M-Bus 900/900S.

The following list will explain how to install software in the PiiGAB M-Bus 900 V2 and PiiGAB M-Bus 900S. These steps are either used to install a new software or update an existing.
Note: If QuickPost, Modbus2MBus or Wireless M-Bus is not shown in the web browser, please press CTRL + F5.
Quick start Guide to Configure M-Bus to Modbus
1. Plug all the meters you want to use on the M-bus loop into Mbus Master ports 1-4 on your Gateway.
2. Search your meters in the web interface using a "Fast Search" in the Startup Config tab

Your meters should appear in a list under the "Fast Search" button
3. Go to the overview page in Startup Config where the meters should now be visible in the list below.

Add Encryption Keys to the meters if they are Wireless meters
4. Click on "Auto-Create Myconfig files"

The files to be used to read meters are now created
5. Go to MbusHub and the tab "Master port", then select the configuration file for the Master port file as shown below. Save the configuration.

6. Go to Slave Port 1 and select the configuration file as shown below

7. Now you will be able to query against the registry entries described in the CSV file located in the slave ports tab of the web interface

Quick start Guide to Configure M-Bus to Modbus
1. Plug all the meters you want to use on the M-bus loop into Mbus Master ports 1-4 on your Gateway.
2. Search your meters in the web interface using a "Fast Search" in the Startup Config tab

Your meters should appear in a list under the "Fast Search" button
3. Go to the overview page in Startup Config where the meters should now be visible in the list below.

Add Encryption Keys to the meters if they are Wireless meters
4. Click on "Auto-Create Myconfig files"

The files to be used to read meters are now created
5. Go to MbusHub and the tab "Master port", then select the configuration file for the Master port file as shown below. Save the configuration.

6. Go to Slave Port 1 and select the configuration file as shown below

7. Now you will be able to query against the registry entries described in the CSV file located in the slave ports tab of the web interface

Conversion of Modbus meters to M-Bus is done in the program Modbus2Mbus Config. You can find this for download at https://www.piigab.com/products/mjukvara/
In order to have a simple and trouble-free conversion, it is important to have the meter's manual available.
Create a new project and then add a device per meter.
Set the parameters for Mbus and Modbus communication
Add objects for each measured value to be read out and set the correct Modbus register as well as unit and scaling.
If you have several meters of each type, copy the meter and only change the Slave and M-Bus address.
It is also possible to save these as templates for future projects.
After the project is finished, it is saved and then uploaded to the 900
If the communication does not work, check that no other process locks that port.
Check that Modbus2Mbus or any slave port is not set to RS485.
Also enable RS-485 Failsafe in MBushub for more stable collection.

The following list instructs how to configure a PiiGAB M-Bus 900/900S so that M-Bus meters can be read with RS485.
The picture shows Slave port 2 is configured for RS485 on 2400 baud, 8 data bits, even parity, 1 stop bit, 2000ms as timeout and M-Bus communication.

Note:

Can't find the information you are looking for? Let us know with an email to support@piigab.se. We also want to recommend our manuals and our "getting started" documents that you will find under downloads section in the respective product. The documents include valuable information on how to proceed.
If you are looking for features or if you find that something is not working as expected, do not hesitate to contact us so we can adjust the help files or include the features at the next update. If there is anything that you feel is missing or if you have ideas on how to make it better, let us know.
Phone: +46 (0) 31-55 99 77
Email: info@piigab.se
About cookies
Integrity policy/GDPR
PiiGAB applies "Allmänna bestämmelser NL 17"
PiiGAB Processinformation i Göteborg AB
Visiting address: Analysvägen 3
Delivery: Kalkylvägen 1
435 33 MölnlyckeSweden
Account Number: 1821313184
Branch: 9960
IBAN: SE73 9500 0099 6018 2131 3184
Swift/BIC: NDEASESS
Account holder: PiiGAB Processinformation i Göteborg AB
Bank: Nordea Bank Abp, Sweden

