FAQ
Here you can find a number of questions and answers regarding our products.
Here you can find a number of questions and answers regarding our products.
Here is an example of how to setup the initial contact with a PiiGAB M-Bus 810.
Now you should see the PiiGAB M-Bus Setup display the PiiGAB M-Bus 810 in the list. Check the MAC-address and that the IP-address should be set to 192.168.10.2.
Here is an example of how to setup the initial contact with a PiiGAB M-Bus 900.
Now you should see the PiiGAB M-Bus Setup display show the PiiGAB M-Bus 900 in the list. Check the MAC-address and the IP-address should be 192.168.10.2.
Vissa mätare hanterar inte SND_NKE tillsammans med REQ_UD2 . Klicka ur alternativet SND_NKE så borde mätarna svara.
To troubleshoot M-Bus meters connected to an PiiGAB M-Bus 810 there are a couple of things to verify.
Here is a list of good tools to use during troubleshooting:
IP-address
What IP-address is the gateway using? To have network communication with the gateway you need to setup your computer in the same network as the gateway. If there is an IT section please contact them to receive an IP-address for your computer. With the PiiGAB M-Bus Setup Wizard you can search gateways on the network or ping the gateway’s IP-address to verify if the network communication works.
I PiiGAB M-Bus Wizard kan man söka efter omvandlare på nätverket eller ”pinga” omvandlarens IP-adress för att verifiera att nätverkskontakten fungerar.
f it’s not possible to receive the gateway’s IP-address then you need to setup a new IP-address.
Please see the FAQ on how to do this.
Port
What port is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the port with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Protocol
What protocol is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the protocol with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Note: If the gateway uses TCP you might not be able to connect to the gateway with the PiiGAB M-Bus Setup Wizard to read the M-Bus meters. This is due to that another client is connected to the port that the gateway is using. Change the port, change to UDP or turn off the client.
Communication speed
What communication speed is the gateway set to in order for the the M-Bus client to read the M-Bus meters?If you have network connection with the gateway you can find out the communication speed with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Note: If the gateway is set to 300 baud the communication speed is very slow. Remember to change the timeout in the PiiGAB M-Bus Setup Wizard to handle the long response time.
M-Bus meters
Is there any documentation of what M-Bus meters that are connected to the gateway? What addresses does the M-Bus meters use? (primary or secondary addresses).
If there is documentation of the meters then you can simple check each meter one by one with the PiiGAB M-Bus Setup Wizard. It’s also possible to read the search function in the PiiGAB M-Bus Setup Wizard.
If there is no documentation of the meters then you can use the search function in the PiiGAB M-Bus Setup Wizard. If the the result of the search function is incomplete then you have to find each meter one by one on the site and test them individually by it’s M-Bus address (primary or secondary address).
A M-Bus meter not responding
If an M-bus meter is not responding then you have to test the meter individually. If possible disconnect all other meters and test only that specific meter. Try with primary address 254 or the meter’s own primary or secondary address.
If it’s not possible to disconnect all meters then you can test the specific meter with a MicroMaster USB.
Det är bara PiiGAB M-Bus 900 V2.XX.XX.XXX eller senare versioner som stödjer funktionen där IP-adressen kan ändras med PiiGAB M-Bus Wizard.
Both PiiGAB M-Bus 900 V2 and PiiGAB M-Bus 900S can change their IP address with the PiiGAB M-Bus Wizard.
Keep in mind that the netmask and default gateway will not be set. These need to be set in the converter's web interface. Please read it under the FAQ section "Example of initial contact"
If you are using TCP and the M-Bus Wizard at the same time you cannot make contact with an additional TCP client since the M-Bus Wizard “owns” the TCP handle. Shut down the M-Bus Wizard before starting the second TCP client. The same goes if you are using COM ports.
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
300 Baudrate | 2400 Baudrate | 9600 Baudrate | |
Master port | 9600ms | 1300ms | 400ms |
Slave port | 9600ms | 1300ms | 400ms |
SND_NKE | 11000ms | 1500ms | 600ms |
REQ_UD2 | 11000ms | 1500ms | 600ms |
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
300 Baudrate | 2400 Baudrate | 9600 Baudrate | |
Master port | 9600ms | 1300ms | 400ms |
Slave port | 9600ms | 1300ms | 400ms |
SND_NKE | 11000ms | 1500ms | 600ms |
REQ_UD2 | 11000ms | 1500ms | 600ms |
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Port 30718 över UDP/IP används i följande funktioner:
Övriga funktioner i PiiGAB M-Bus Wizard anger man själv vilken port och protokoll som ska användas.
Specifikt för Hitta omvandlare på nätverket
Funktionen Find gateways on your network. använder broadcast adressen (255.255.255.255) för att hitta PiiGAB M-Bus 810 och PiiGAB M-Bus 900/900S på nätverket. Tänk på att broadcast kan vara inaktiverat i routrar. Detta kan orsaka att man inte kan hitta omvandlare som är placerade på andra subnät.
To troubleshoot M-Bus meters connected to an PiiGAB M-Bus 810 there are a couple of things to verify.
Here is a list of good tools to use during troubleshooting:
IP-address
What IP-address is the gateway using? To have network communication with the gateway you need to setup your computer in the same network as the gateway. If there is an IT section please contact them to receive an IP-address for your computer. With the PiiGAB M-Bus Setup Wizard you can search gateways on the network or ping the gateway’s IP-address to verify if the network communication works.
I PiiGAB M-Bus Wizard kan man söka efter omvandlare på nätverket eller ”pinga” omvandlarens IP-adress för att verifiera att nätverkskontakten fungerar.
f it’s not possible to receive the gateway’s IP-address then you need to setup a new IP-address.
Please see the FAQ on how to do this.
Port
What port is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the port with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Protocol
What protocol is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the protocol with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Note: If the gateway uses TCP you might not be able to connect to the gateway with the PiiGAB M-Bus Setup Wizard to read the M-Bus meters. This is due to that another client is connected to the port that the gateway is using. Change the port, change to UDP or turn off the client.
Communication speed
What communication speed is the gateway set to in order for the the M-Bus client to read the M-Bus meters?If you have network connection with the gateway you can find out the communication speed with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Note: If the gateway is set to 300 baud the communication speed is very slow. Remember to change the timeout in the PiiGAB M-Bus Setup Wizard to handle the long response time.
M-Bus meters
Is there any documentation of what M-Bus meters that are connected to the gateway? What addresses does the M-Bus meters use? (primary or secondary addresses).
If there is documentation of the meters then you can simple check each meter one by one with the PiiGAB M-Bus Setup Wizard. It’s also possible to read the search function in the PiiGAB M-Bus Setup Wizard.
If there is no documentation of the meters then you can use the search function in the PiiGAB M-Bus Setup Wizard. If the the result of the search function is incomplete then you have to find each meter one by one on the site and test them individually by it’s M-Bus address (primary or secondary address).
A M-Bus meter not responding
If an M-bus meter is not responding then you have to test the meter individually. If possible disconnect all other meters and test only that specific meter. Try with primary address 254 or the meter’s own primary or secondary address.
If it’s not possible to disconnect all meters then you can test the specific meter with a MicroMaster USB.
If you are using TCP and the M-Bus Wizard at the same time you cannot make contact with an additional TCP client since the M-Bus Wizard “owns” the TCP handle. Shut down the M-Bus Wizard before starting the second TCP client. The same goes if you are using COM ports.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Vissa mätare hanterar inte SND_NKE tillsammans med REQ_UD2 . Klicka ur alternativet SND_NKE så borde mätarna svara.
To troubleshoot M-Bus meters connected to an PiiGAB M-Bus 810 there are a couple of things to verify.
Here is a list of good tools to use during troubleshooting:
IP-address
What IP-address is the gateway using? To have network communication with the gateway you need to setup your computer in the same network as the gateway. If there is an IT section please contact them to receive an IP-address for your computer. With the PiiGAB M-Bus Setup Wizard you can search gateways on the network or ping the gateway’s IP-address to verify if the network communication works.
I PiiGAB M-Bus Wizard kan man söka efter omvandlare på nätverket eller ”pinga” omvandlarens IP-adress för att verifiera att nätverkskontakten fungerar.
f it’s not possible to receive the gateway’s IP-address then you need to setup a new IP-address.
Please see the FAQ on how to do this.
Port
What port is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the port with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Protocol
What protocol is the gateway set to in order for the the M-Bus client to read the M-Bus meters? If you have network connection with the gateway you can find out the protocol with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Note: If the gateway uses TCP you might not be able to connect to the gateway with the PiiGAB M-Bus Setup Wizard to read the M-Bus meters. This is due to that another client is connected to the port that the gateway is using. Change the port, change to UDP or turn off the client.
Communication speed
What communication speed is the gateway set to in order for the the M-Bus client to read the M-Bus meters?If you have network connection with the gateway you can find out the communication speed with the PiiGAB M-Bus Setup Wizard.
Starta PiiGAB M-Bus Wizard -> Ändra omvandlarens parametrar -> Anslut via nätverk.
Note: If the gateway is set to 300 baud the communication speed is very slow. Remember to change the timeout in the PiiGAB M-Bus Setup Wizard to handle the long response time.
M-Bus meters
Is there any documentation of what M-Bus meters that are connected to the gateway? What addresses does the M-Bus meters use? (primary or secondary addresses).
If there is documentation of the meters then you can simple check each meter one by one with the PiiGAB M-Bus Setup Wizard. It’s also possible to read the search function in the PiiGAB M-Bus Setup Wizard.
If there is no documentation of the meters then you can use the search function in the PiiGAB M-Bus Setup Wizard. If the the result of the search function is incomplete then you have to find each meter one by one on the site and test them individually by it’s M-Bus address (primary or secondary address).
A M-Bus meter not responding
If an M-bus meter is not responding then you have to test the meter individually. If possible disconnect all other meters and test only that specific meter. Try with primary address 254 or the meter’s own primary or secondary address.
If it’s not possible to disconnect all meters then you can test the specific meter with a MicroMaster USB.
Det finns tre timeouter i PiiGAB M-Bus Wizard för de tre protokollen M-Bus, Modbus och MBusASCII. Ställ respektive timeout enligt hur lång tid det tar att få svar på varje fråga som PiiGAB M-Bus Wizard skickar.
Obs: För äldre versioner av PiiGAB M-Bus Wizard (3.1.0. eller tidigare) var det samma timeout för de tre olika protokollen.
För att ställa respektive timeout gör följande:
Det är bara PiiGAB M-Bus 900 V2.XX.XX.XXX eller senare versioner som stödjer funktionen där IP-adressen kan ändras med PiiGAB M-Bus Wizard.
Öka värdet på M-BusTimeout. PiiGAB M-Bus Wizard gör säkert timeout då svaret från mätaren inte hunnit komma in. Tryck på Debug/Verktygsmeny/Tidsfördröjningar. Ändra värdet på M-BusTimeout till 10000 millisekunder.
Both PiiGAB M-Bus 900 V2 and PiiGAB M-Bus 900S can change their IP address with the PiiGAB M-Bus Wizard.
Keep in mind that the netmask and default gateway will not be set. These need to be set in the converter's web interface. Please read it under the FAQ section "Example of initial contact"
If you are using TCP and the M-Bus Wizard at the same time you cannot make contact with an additional TCP client since the M-Bus Wizard “owns” the TCP handle. Shut down the M-Bus Wizard before starting the second TCP client. The same goes if you are using COM ports.
Detta beror på att ett eller flera nätverkskort har fått en annan konfiguration under tiden PiiGAB M-Bus Wizard kördes. Exempelvis om man byter IP-adress på ett nätverkskort.
PiiGAB M-Bus Wizard läser in tillgängliga nätverkskort under uppstart och när felet uppstod finns det en felande länk till nätverkskorten.
Vänligen starta om PiiGAB M-Bus Wizard.
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
300 Baudrate | 2400 Baudrate | 9600 Baudrate | |
Master port | 9600ms | 1300ms | 400ms |
Slave port | 9600ms | 1300ms | 400ms |
SND_NKE | 11000ms | 1500ms | 600ms |
REQ_UD2 | 11000ms | 1500ms | 600ms |
If the search of secondary addresses failes in the PiiGAB M-Bus Setup Wizard through a PiiGAB M-Bus 900/900S then the timeouts are probably set too high.
There are four timeouts that are required to configure:
This table shows how to configure the tiemouts depending on the communication speed:
300 Baudrate | 2400 Baudrate | 9600 Baudrate | |
Master port | 9600ms | 1300ms | 400ms |
Slave port | 9600ms | 1300ms | 400ms |
SND_NKE | 11000ms | 1500ms | 600ms |
REQ_UD2 | 11000ms | 1500ms | 600ms |
Ett felmeddelande visar att en OCX-fil saknas när PiiGAB M-Bus Wizard startar.
Exempelvis:
Felet beror på att den angivna systemfilen saknas i Windows installationen.
För att lösa problemet:
1) Sök efter filen som saknas. Prova leta i OCX-dump.
2) Spara OCX-filen i mappen C:\Windows\SysWOW64\.
3) Starta terminalen.
4) Kör kommandot: regsvr32 ”C:\Windows\SysWOW64\mscomm32.ocx”.
OBS: Det kan behövas att terminalen körs med administratörs rättigheter.
Nu ska PiiGAB M-Bus Setup starta.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
Make sure the computer and the gateway are configured within the same IP-address range. If the gateway is placed in a subnet, the PiiGAB M-Bus Setup Wizard will not be able to find the gateway.
För nyare operativsystem än Windows XP är C:\Program files inte passande som installationskatalog. Det krävs administratörsrättigheter för att skriva till katalogen. Är du en användare som inte har administratörsrättigheter måste PiiGAB M-Bus Wizard i så fall installeras under en annan systemkatalog. Vi föreslår installation direkt under C:\, exempelvis C:\PiiGAB_M-Bus_Wizard
Port 30718 över UDP/IP används i följande funktioner:
Övriga funktioner i PiiGAB M-Bus Wizard anger man själv vilken port och protokoll som ska användas.
Specifikt för Hitta omvandlare på nätverket
Funktionen Find gateways on your network. använder broadcast adressen (255.255.255.255) för att hitta PiiGAB M-Bus 810 och PiiGAB M-Bus 900/900S på nätverket. Tänk på att broadcast kan vara inaktiverat i routrar. Detta kan orsaka att man inte kan hitta omvandlare som är placerade på andra subnät.
Can't find the information you are looking for? Let us know with an email to support@piigab.se. We also want to recommend our manuals and our "getting started" documents that you will find under downloads section in the respective product. The documents include valuable information on how to proceed.
If you are looking for features or if you find that something is not working as expected, do not hesitate to contact us so we can adjust the help files or include the features at the next update. If there is anything that you feel is missing or if you have ideas on how to make it better, let us know.
Phone: +46 (0) 31-55 99 77
Email: info@piigab.se
About cookies
Integrity policy/GDPR
PiiGAB applies "Allmänna bestämmelser NL 17"
PiiGAB Processinformation i Göteborg AB
Visiting address: Analysvägen 3
Delivery: Kalkylvägen 1
435 33 MölnlyckeSweden
Account Number: 1821313184
Branch: 9960
IBAN: SE73 9500 0099 6018 2131 3184
Swift/BIC: NDEASESS
Account holder: PiiGAB Processinformation i Göteborg AB
Bank: Nordea Bank Abp., Sweden
We use cookies to ensure you the best experience on our website. If you continue to use this website, we will assume that you accept our cookies.
ApproveWe may request cookies to be set on your device. We use cookies to let us know when you visit our websites, how you interact with us, to enrich your user experience, and to customize your relationship with our website.
Click on the different category headings to find out more. You can also change some of your preferences. Note that blocking some types of cookies may impact your experience on our websites and the services we are able to offer.
These cookies are strictly necessary to provide you with services available through our website and to use some of its features.
Because these cookies are strictly necessary to deliver the website, refuseing them will have impact how our site functions. You always can block or delete cookies by changing your browser settings and force blocking all cookies on this website. But this will always prompt you to accept/refuse cookies when revisiting our site.
We fully respect if you want to refuse cookies but to avoid asking you again and again kindly allow us to store a cookie for that. You are free to opt out any time or opt in for other cookies to get a better experience. If you refuse cookies we will remove all set cookies in our domain.
We provide you with a list of stored cookies on your computer in our domain so you can check what we stored. Due to security reasons we are not able to show or modify cookies from other domains. You can check these in your browser security settings.
These cookies collect information that is used either in aggregate form to help us understand how our website is being used or how effective our marketing campaigns are, or to help us customize our website and application for you in order to enhance your experience.
If you do not want that we track your visit to our site you can disable tracking in your browser here:
We also use different external services like Google Webfonts, Google Maps, and external Video providers. Since these providers may collect personal data like your IP address we allow you to block them here. Please be aware that this might heavily reduce the functionality and appearance of our site. Changes will take effect once you reload the page.
Google Webfont Settings:
Google Map Settings:
Google reCaptcha Settings:
Vimeo and Youtube video embeds:
The following cookies are also needed - You can choose if you want to allow them:
You can read about our cookies and privacy settings in detail on our Privacy Policy Page.