Viltrus Converter Mbus2RS485
250 loads

Mbus connects to Converter terminals 1 and 2 - polarity independent
If connected correctly, Operating should be flashing and Offline and Overload should be off.
(in case of few loads, Offline may still be lit)
RS485 between Converter and Piigab
T+/R+ (3) on the Converter is connected to RS485 A (8) on Piigab
T-/R- (4) on the Converter is connected to RS485 B (9) on the Piigab
GND (5) on the Converter is connected to GND (10) on the Piigab

| Plinth | Details |
| 1 | Mbus + |
| 2 | Mbus |
| 3 | RS485 TD(A+) |
| 4 | RS485 TD(B-) |
| 5 | RS485 GND |
| 6 | 230V GND |
| 7 | 230V N |
| 8 | 230V L |

Comment on this FAQ